Wuhan Huaying HYVA 404 CT/PT Tester 

WUHAN HUAYING HYVA 404 CT/PT Tester 
  • CT parameters check in work burden & CT transient parameters analysis
  • Secondary loop burden measurement & Error line curve test for protection CT
  • CT Secondary burden Range 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm)

Product Details

WUHAN HUAYING HYVA 404 CT/PT Tester

Application

Tests for current transformer:

1)Excitation curve and parameters test
2)Turns ratio test
3)Ratio and phase error test
4)Polarity mark check
5)Coil resistance measurement
6)Secondary loop burden measurement
7)Error line curve test for protection CT
8)Transient CT parameters test
9)CT nameplate guess

Tests for voltage transformer:

1)Excitation curve test
2)Turns ratio test
3)Polarity test
4) Secondary burden test
5) Coil resistance test

Applications for CTPT analyzer:

1) CT nameplate check
2) CT parameters check in work burden
3) CT transient parameters analysis
4) CT ratio and phase error calibration
5) PT routine test

CTPT analyzer technical index

1 Test standards: IEC60044-1, IEC60044-6, GB1208, GB16847, C57.13
2 Power supply: AC220V±10%,50Hz/60Hz±10%
3 Power output: 0.1~125V (AC)
4 Current output: 0.001~5A(RMS)
5 Power output:300VA
6 Current measurement:
Range:0~10A (automatically change range in 0.1/0.4/2/10A)
Error <±0.1%+0.01%FS
7 Voltage measurement:
Range:0~200 V (automatically change range in 1V/10V/70V/200V)
Error < ±0.1%+0.01%FS
8 Turns ratio measurement:
Range :1~10000,
1~1000 error<0.05%
1000~2000 error<0.1%
2000~10000 error<0.2%
9 Phase measurement: error:±2min,resolution:0.01min
10 Coil resistance measurement:
Range:0~8kO (automatically change range in 2ohm/20ohm/80ohm/800ohm/8kohm)
Error< 0.1%+0.01%FS
Maximum resolution:0.1mO
11 Temperature measurement:-50~100 Celsius degree, error<3 Celsius degree
12 CT Secondary burden:
Range 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm)
Error <0.1%+0.01ohm
Maximum resolution 0.001ohm
13 PT Secondary burden:
Range 0~80kohm (automatically change range in 800ohm/8kohm/80kohm)
Error <0.2%+0.02%FS
Maximum resolution: 0.1ohm
14 Saved data groups:>1000groups
15 Work condition: Temperature:-10?~50?, moist:=90%
16 Size: 485mm×356mm×183mm
17 Weight: <13Kg

PONOVO PCT 200i CT and PT Test Equipment PCT200i is specially designed for current transformer characteristic test. Compared with PCT200Li,PCT200i owns more test items and higher technica...
PONOVO PCT 200Ai CT and PT Test Equipment PCT200Ai is the CT/PT test set can finish various tests of different transformers. Compared with PCT200i,its accuracy is higher. This CT analyzer...
PCT200i is specially designed for current transformer characteristic test. Compared with PCT200Li,PCT200i owns more test items and higher technical parameters.This CT analyzer can finish the...
PONOVO PCT 200i CT and PT Test Equipment PCT200i is specially designed for current transformer characteristic test. Compared with PCT200Li,PCT200i owns more test items and higher technica...
WUHAN HUAYING HYVA 403 CT/PT Tester General introduction HYVA-403 CT analyzer is special tester for current transformer. It takes IPC as core to sample and data process. The instrumen...