Mirus GENLINK Dissimiliar Pitch Neutral Limiter

MIRUS GENLINK Dissimilar Pitch Neutral Limiter 
  • Reduces neutral circulating current by >75%
  • It can be used in both 3-wire and 4-wire systems
  • Eliminates generator overheating and false protection trips caused by triple frequency circulating currents

Product Details

MIRUS GENLINK Dissimilar Pitch Neutral Limiter

GENLINK DPNL is a multiple winding reactor and when installed in the common neutral of paralleled sources either between the dissimilar generators or the generator and the Utility supply it can greatly reduce the neutral circulating currents that result from the instantaneous voltage differences. These neutral circulating currents, which are predominantly triple frequency, have the potential to cause a considerable amount of damage with respect to overheating generators and causing false-protection trips.

Voltage differences in paralleled generators made by different manufacturers or differences in standard pitch design configurations in generators made by the same manufacturer can result in heavy neutral circulating currents. Additionally, alternative energy sources such as solar and wind power that generates AC power can introduce heavy circulating currents in 4-wire parallel applications. GENLINK when applied, will impede the flow of circulating currents while adding only minimal impedance to the fault current path.

GENLINK DPNL can be used in both 3-wire and 4-wire systems. For 4-wire applications where there is return neutral current from 1-Ph loads, the DPNL must be sized for this current as well as the circulating current. For 3-wire applications where there is no return neutral current from 1-Ph loads, a smaller size DPNL can be used. Grounding of the neutral must be done at only one location which is recommended to be the distribution switchboard.

Features

• Inserts >40% impedance in neutral current circulating path
• Reduces neutral circulating current by >75%
• Adds <1% saturated impedance to 1-Ph fault path
• No impedance to 3-Ph fault path
• Use in 3-wire or 4-wire applications or any parallel source application with a common neutral and dissimilar voltage waveforms
• Eliminates generator overheating and false protection trips caused by triple frequency circulating currents
• Easy to install
• Reliable and proven performance

MIRUS 5-13 Neutral Current Eliminator 3-phase, 3-wire autotransformers with 30°, 15° or 20° phase shift between input and output. They are connected in series with the supply to variable ...
MIRUS Lineator HP Harmonic Mitigation Filters The Lineator High Performance (HP) model is used where the highest power quality demands must be met. Lineator HP outperforms active filters ...
MIRUS Onics Harmonic Mitigating Power Center The Onics HMPC is an outstanding power distribution unit ideal for the raised floor environment. It incorporates MIRUS' patented and proven Ha...
MIRUS Drive 24 Transformers Multiple output auto or isolation transformers ideally suited for reduction of harmonics generated by VFDs or other 3-phase rectifier loads. Drive 12/24â„¢ pr...
MIRUS Drive Tamers Transformers Designed to replace standard drive isolation transformers, the Drive Tamerâ„¢ is built to not only withstand the harsh harmonic environment produced by Varia...