Free Call Australia : 1 800 834 991

Related Products

HIOKI PW3365 Clamp On Power Logger

HIOKI PW3365 Clamp On Power Logger New
  • Designed for 50/60 Hz commercial line use
  • 3 circuits (1P2W), single circuit (1P3W, 3P3W, 3P4W)
  • Save data to the SD card continuously
  • (Current) Clamp input
  • (Voltage) Non-metallic contact sensor

Product Details

HIOKI PW3365 Clamp On Power Logger are multi-channel power measuring devices utilizing clamp sensor input to accurately and safely measure power on single-phase to three-phase lines. The PW3365 power logger takes safety and convenience one step further by being the world’s first non-metallic contact power meter that utilizes completely covered voltage clips that can be attached to any part of a cable or busbar. Customers can now monitor power demand and other power parameters to aid in energy audits and validate energy saving measures without risk of short-circuit accidents, power interruptions, or bodily injury due to electrocutions.

Key Features
• The PW3365’s dedicated voltage sensor delivers the world’s first no-metal-contact measurement.
• Supports single to three-phase, 4-wire circuits
• Measure between 90V to 520V
• Slim, compact design that can be placed anywhere
• Store months of data on SD cards
• The QUICK SET function guides you in making the right connections

Basic Specifications
Measurement line & number of circuits : 50/60 Hz, Single phase 2 wires (1/2/3 circuits), Single phase 3 wires (1 circuit), Three phases 3 wires (1 circuit), Three phases 4 wires (1 circuit), Current only: 1 to 3 channels

Measurement items : Voltage RMS, current RMS, voltage fundamental wave value, current fundamental wave value, voltage fundamental wave phase angle, current fundamental wave phase angle, frequency (U1), voltage waveform peak (absolute value), current waveform peak (absolute value), active power, reactive power, apparent power, power factor (with lag/lead display) or displacement power factor (with lag/lead display), active energy (consumption, regeneration), reactive energy (lag, lead), energy cost display, active power demand quantity (consumption, regeneration), reactive power demand quantity (lag, lead), active power demand value(consumption, regeneration), reactive power demand value (lag, lead), power factor demand

Voltage ranges : 400 V AC (Effective measurement range: 90.0 V to 520.0 V)

Current ranges : 500.00 mA to 5.0000 kA AC (depends on current sensor in use),
50.000 mA to 5.0000 A AC (Leak clamp on sensor only)

Power ranges : 200.00 W to 6.0000 MW (depends on voltage/current combination and measured line type)

Basic accuracy : Voltage : ±1.5% rdg. ±0.2% f.s(combined accuracy with PW3365-20 + PW9020)
Current : ±0.3% rdg. ±0.1% f.s. + clamp sensor accuracy
Active power : ±2.0% rdg. ±0.3% f.s. + clamp sensor accuracy (at power factor = 1)

Display update rate : 0.5 sec (except when accessing SD card or internal memory, or during LAN/USB communication)

Save destination : SD Memory card, or internal memory at real time

Data save interval : 1 sec to 30 sec, 1 minute to 60 minutes, 14 selections

Save items : Measurement value save: Average only / Average, Maximum, Minimum value
Screen copy: BMP form (saved every 5 min. at minimum interval time)
Waveform save: Binary waveform data

Interfaces : SD memory card
HTTP server function, remote settings via communication program, data download
USB 2.0: When connected to a PC, the SD Card and internal memory are recognized as removable storage devices, remote settings via communication program, data download
Pulse output: proportional to active power consumption when measuring integral power consumption, Isolated open-collector signal

Functions : Connection check, Quick Set navigation guide, clock

Power supply : AC adapter Z1008: (100 to 240 V AC, 50/60 Hz), 45 VA (including AC adapter)
Battery pack 9459: (DC 7.2 V, 3 VA, charging time 6 hr 10 m), 5 hours of continuous use (with back light off)

Dimensions and mass : 180 mm (7.09 in)W × 100 mm (3.94 in)H × 48 mm (1.89 in)D, 540 g (19 oz) without PW9002
180 mm (7.09 in)W × 100 mm (3.94 in)H × 68 mm (2.68 in)D, 820 g (28.9 oz) with PW9002

Accessories : Safety Voltage Sensor PW9020 ×1 set, AC adapter Z1008 ×1, USB cable ×1, Instruction manual ×1, Measurement guide ×1, Color spiral tubes ×1 set: red, yellow, blue/four each, Spiral tubes for grouping clamp sensor cords ×10

Product Description

HIOKI PW3365 Clamp On Power Logger is the world’s first non-metallic contact power logger.Supports single to three-phase, 4-wire circuits.Store months of data on SD cards.

HIOKI 3169-20 Clamp-On Power HiTester • Monitor Power & Demand management at single-phase 4-circuits, three-phase 2-circuits, and harmonic analyse simultaneously. • Measure V, A, W, VA, Var,...
ELSPEC G4400 BLACKBOX Fixed Power Quality Analyzer The revolutionary ELSPEC G4000 BLACKBOX is the next generation in power quality analyzers. The G4K provides accurate detection and isola...
HIOKI PW3198 Power Quality Analyzer The New World Standard for Power Quality Analysis, with recording & analyzing according to Class A requirements for PQAs Verify power problems in acco...
ELSPEC BLACKBOX Firmware Release. Class A: Extended support per latest 61000-4-30 Class A revision. Many new parameters, averaged intervals, and more! Device Configuration FILE: Based on X...
ELSPEC Power IQ Software. Power quality analysis software that works in parallel with the on-board analyzer or controller, displaying system status and measurement results in a Windows opera...