Hioki 3198 Power Quality Analyzer IEC61000-4-30 Class A Standard – PW 3198 PQA

HIOKI 3198 Power Quality Analyzer IEC61000-4-30 Class A Standard – PW 3198 PQA 
  • Verify power problems in accordance with the IEC61000-4-30 Class A standard
  • Broadband voltage range lets you measure even high-order harmonic components of up to 80 kHz
  • Optional GPS BOX for synchronizing multiple devices

Product Details

HIOKI 3198 Power Quality Analyzer IEC61000-4-30 Class A Standard – PW 3198 PQA The New World Standard for Power Quality Analysis, with recording & analyzing according to Class A requirements for PQAs

Verify power problems in accordance with the IEC61000-4-30 Class A standard. High Accuracy and continuous gapless recording (V:±0.1% of nominal voltage, A and W:±0.2% rdg. ±0.1% f.s.). CAT IV 600V - safe enough for incoming power lines. Broadband voltage range lets you measure even high-order harmonic components of up to 80 kHz. Wide dynamic range from low voltages up to 1300V (3P4W line-to-line voltage). Maximum 6000V transient overvoltage up to 700kHz. LAN, USB and SD card interfaces. Optional GPS BOX for synchronizing multiple devices.

Voltage can be measured with the main unit alone. An optional current sensor is necessary to measure current or power parameters. Use Model 9624-50 PQA-HiVIEW PRO (version 2.00 or later) with a PC to analyze the data collected to the SD card.

Measurement line type : Single-phase 2-wire, Single-phase 3-wire, Three-phase 3-wire or Three-phase 4-wire plus one extra input channel (must be synchronized to reference channel during AC/DC measurement)

Voltage ranges : Voltage measurement: 600.00 V rms

Transient measurement : 6.0000 kV peak

Current ranges : 500.00 mA to 5.0000 kA AC (depends on current sensor in use)

Basic accuracy : Voltage: ±0.1% of nominal voltage

Current : ±0.2% rdg. ±0.1% f.s. + current sensor accuracy

Active power : ±0.2% rdg. ±0.1% f.s. + current sensor accuracy

Measurement items :
1. Transient over voltage : 2MHz sampling.
2. Frequency cycle : Calculated as one cycle, 40 to 70Hz
3. Voltage (1/2) RMS: one cycle calculation refreshed every half cycle.
Current (1/2) RMS: half-cycle calculation.
4. Voltage swell, Voltage dips, Voltage interruption
5. Inrush current
6. Voltage waveform comparison
7. Instantaneous flicker value: As per IEC61000-4-15
8. Frequency: Calculated as 10 or 12 cycles, 40 to 70Hz
9. 10-sec frequency: Calculated as the whole-cycle time during the specified 10s period, 40 to 70Hz
10. Voltage waveform peak, Current waveform peak
11. Voltage, Current, Active power, Apparent power, Reactive power, Active energy, Reactive energy, Power factor, Displacement power factor, Voltage unbalance factor, Current unbalance factor (negative-phase, zero-phase)
12. High-order harmonic component (voltage/ current): 2kHz to 80kHz
13. Harmonic/ Harmonic phase angle (voltage/ current), Harmonic power: 0th to 50th orders
14. Harmonic voltage-current phase angle: 1th to 50th orders
15. Total harmonic distortion factor (voltage/ current)
16. Inter harmonic (voltage/ current): 0.5Hz to 49.5Hz
17. K Factor (multiplication factor)
18. IEC Flicker, ? V10 Flicker

Record : 55 weeks (with repeated recording set to [1 Week], 55 iterations) 35 days (with repeated recording set to [OFF])

Interface : SD/SDHC card, RS-232C, LAN (HTTP server funtion), USB2.0

Display : 6.5-inch TFT color LCD (640×480 dots)

Power supply : AC ADAPTER Z1002 (12V DC, Rated power supply 100V AC to 24 V AC, 50/60Hz)

BATTERY PACK Z1003 (Ni-MH 7.2V DC 4500mAh)

Dimensions, mass 300mm(11.81in)W × 211mm(8.31in)H × 68mm(2.68in)D (excluding protrusions), 2.6kg(91.7oz) (including battery pack)

Supplied accessories : Instruction manual×1, Measurement guide×1, VOLTAGE CORD L1000×1 set, Spiral Tube×1, Input Cable Labels×1, AC ADAPTER Z1002×1, Strap×1, USB cable (1m 3.28ft length)×1, BATTERY PACK Z1003×1, SD MEMORY CARD 2GB Z4001×1

HIOKI 3169-20 Clamp-On Power HiTester • Monitor Power & Demand management at single-phase 4-circuits, three-phase 2-circuits, and harmonic analyse simultaneously. • Measure V, A, W, VA, Var,...
FLUKE 1744 Basic Three-Phase Power Quality Logger - Power Quality Logger Memobox Excl. current clamps FS17xx Power quality logging is easy with a compact and rugged Fluke power meter. The...
HIOKI PW3198 Power Quality Analyzer The New World Standard for Power Quality Analysis, with recording & analyzing according to Class A requirements for PQAs Verify power problems in acco...
HIOKI 3196 Power Quality Analyzer Monitor and record the quality of power to analyze the cause of trouble when it occurs! HIOKI 3196 Power Quality Analyzer is your most reliable and compl...
HIOKI 3197 Power Quality Analyzer The most comprehensive portable PQA on the market. Catch power quality problems on the fly, before they catch you Monitor for : Inrush current, Voltage ...